Cabinet Rental — 21U and 42U
Cabinet rental means renting a whole locked rack, or half of one, in the data centre. The difference from placing individual servers is this: you arrange the inside of the rack, install your own switch and cabling, and the space is allocated to you alone. It is the right structure for teams running several servers or bringing their own network equipment.
What is a U, and how many servers fit?
Cabinet height is measured in rack units; 1U is about 4.45 cm. A typical 1U server occupies exactly that, while 2U servers take two units. In theory twenty-one 1U servers fit in a 21U cabinet, but that is not how it is filled in practice: you need room for a switch, cable management, a power distribution unit and airflow. A realistic plan is 12 to 15 servers in 21U and 28 to 32 in 42U.
21U or 42U?
21U is a half cabinet with room for a few servers, a switch and a power unit. It suits single-project setups and teams planning to grow gradually. 42U is a full cabinet, letting you host dense installations, separate storage units and your own network equipment together. If you run infrastructure for several projects or customers, that is the right starting point. Choose based on your twelve-month estimate rather than today's server count — changing cabinets means moving.
Power and cooling
What decides a cabinet is not only height but the power commitment. Densely placed servers draw more electricity and produce more heat; if the power budget allocated per cabinet is exceeded, the layout has to change. That is why we ask for the estimated total power draw of your servers at the quote stage.
What sits in the cabinet besides servers
If you plan a cabinet as nothing but a stack of servers, the arithmetic will not hold. The first thing that goes in is the power distribution unit (PDU); vertical models mount on the side of the cabinet and consume no U, horizontal ones take 1U or 2U. Then the network: at least one switch (1U), plus a second device for the uplink if you are linking this cabinet to another. Cable management is usually skipped but needed — a 1U cable organiser for every four to six servers is a practical rule that keeps cabling out of the airflow. If you use a patch panel, that is another 1U. Remaining gaps get blanking panels, which are there not for looks but to stop cold air from leaking around to the back of the servers. Add it all up and 5 to 6 U of a 21U cabinet goes to non-server equipment — which is exactly where the 12-to-15-server estimate comes from.
Airflow and temperature: the real limit on density
Height decides how many servers fit in a cabinet; heat decides how many run without trouble. Data centres work on a hot aisle / cold aisle layout: servers take cold air at the front and exhaust warm air at the back, and every device has to face the same way. A single unit mounted backwards pulls its neighbour's hot exhaust into its own intake, and the whole rack pays for it. The widely accepted ASHRAE guidance is to keep server inlet air between 18 and 27 °C; going outside that band raises both failure rates and the electricity the fans themselves consume. A densely packed cabinet draws more power and produces more heat at the same time, so the per-cabinet power budget may well be the limit that fills before the U count does. When you plan, ask how many watts are left as often as how many U are free.
Growth, labelling and the cost of moving
Changing cabinets means moving: cables come out, servers shut down, and bringing everything back up needs a maintenance window. So the size decision is made against your twelve-month estimate rather than today's server count, with at least a fifth added on top. The second practical matter is labelling: which U each server occupies, which switch port it is patched into and which PDU outlet feeds it should live in a written map. Without that map, a remote instruction to restart the third server turns into guesswork. In cabling, too, measuring lengths and securing them is both tidier and better for cooling than leaving surplus cable coiled behind the rack.
How the process works
- 1Choose the cabinet size: 21U for a half cabinet, 42U for a full one.
- 2Set the power commitment; add up the real draw of your servers and leave headroom for growth.
- 3Settle the network plan: are you bringing your own switch, how many uplink ports and at what speed.
- 4Draw the U map; remember to reserve space for the PDU, switch, patch panel and cable management.
- 5Deliver the hardware and have it mounted; record each device's U position and port mapping.
- 6Complete IP, VLAN and rDNS configuration, and put the access procedure in writing — who may enter, how, and with how much notice.
Common mistakes
- Counting U for servers only. A PDU, switch, patch panel and cable management together take 5 to 6 U.
- Leaving empty U without blanking panels. Cold air leaks around to the back of the servers and the devices at the top of the rack run noticeably hotter.
- Confusing the power budget with the U budget. You can hit the power limit while there is still space in the cabinet.
- Leaving cables and ports unlabelled. In a cabinet with no map, every remote instruction becomes guesswork.
- Sizing against today's server count. Growing into a bigger cabinet is a move, with cabling pulled out and a maintenance window needed.
Frequently Asked Questions
- Can I install my own switch?
- Yes. With cabinet rental the inside of the rack is under your control; you can install your own switch, power distribution unit and cabling.
- Is the cabinet locked?
- Yes, cabinets are locked and access is logged. Where on-site work is required, access is arranged in advance.
- How many servers really fit in 21U?
- The arithmetic runs like this: from 21U take 1U for a switch, 1U for a patch panel, 1-2U if you use a horizontal PDU and 2-3U for cable organisers. That leaves 15-16U, so 12 to 15 servers if they are 1U. With 2U servers the number halves.
- Can I bring my own PDU and cables?
- Yes. The equipment inside the cabinet is your choice. Choosing a vertical PDU saves U, and a PDU with remotely switchable outlets lets you power-cycle hardware without anyone going on site.
- What happens when the cabinet fills up?
- Two options: take a second cabinet and link the two over an uplink, or move into a larger one. The first is non-disruptive, the second needs a maintenance window. That is why making the first choice against a twelve-month estimate matters for cost.
- What is the difference between colocation and cabinet rental?
- In colocation you take space per server and the cabinet is shared. With cabinet rental the whole rack is allocated to you; you decide the layout, the switch and the cabling. Colocation suits a handful of servers, cabinet rental suits teams that want to build their own network design.